Q: What does the Ecodesign legislation mean for me?

A: If you commission or install a
new small, medium or large power transformer on or after July 1,
2015, it must legally comply with
the EU Commission Ecodesign requirements. The majority of transformers currently on the market do not comply.


Q: When is the best time to commission a new transformer - should I wait until after July 2015 or act now?

A: Because the combined losses it offers are lower than those specified by the new legislation, the Bowers BEST range could be a more economical and efficient option if you operate your transformer at a load of 35% or more. Commissioning a Bowers BEST unit before July 1, 2015, could not only save you money initially, but in the long-term. The Bowers team can help you assess the options, according to
your use, budget, and energy-saving targets.

Q: Why should I choose Bowers over another transformer manufacturer?

A: Bowers Electricals designs and manufactures here in the UK, supporting local businesses while maintaining a competitive edge against manufacturers who import their products from outside Europe. Bowers
is a family-owned business that prides itself on offering excellent customer service while being noted for the ability and flexibility to provide top-quality, bespoke engineering solutions for each client. With Bowers you can not only
be confident of getting the best value for money but of finding the solution you need – not one you have to work around.


Q: I want amorphous - does Bowers offer an amorphous range?

A: Bowers Electricals is developing a range of

transformers that will meet the stricter requirements of the second phase of Ecodesign legislation, due to come into force in 2021.
In the meantime, Bowers can achieve Tier 1 requirements using the best available core steel technology – keeping cost and size to a minimum. Amorphous core transformers are physically much larger, more expensive and generate significantly higher noise pollution than conventional steel transformers. A study undertaken by members of the Cigrè A2 committee indicates that this increase could be as much as 5dBW(A).
Amorphous is commonly associated with Tier 2 Ecodesign requirements but the EC has committed to reviewing the regulation no later than three years after its entry into force. If minimum values of peak efficiency replace fixed losses the goal posts may move again.


Have a question about the Ecodesign regulations? Get in touch.

High-efficiency oil-immersed transformer compliant with EU Directive 2009/125/EC Manufacturing Standard BSEN 60076 and EN 50464-1

GENERAL SPECIFICATION: Mineral oil-immersed, 50 Hz, three-phase Dyn11 connected ground mounted distribution transformers with the following characteristics:

  • HV voltage = 12kV
  • LV Voltage 415v at no load
  • Free breathing tank with the first filling of
    uninhibited mineral oil compliant with EN 60296 l ONAN natural cooling
  • Indoor / outdoor use
  • Anti-corrosion surface treatment corrosion
    category class C3, as defined by ISO12944-2
  • six position off-circuit tap changer to the HV
    winding providing a voltage variation of +7½% to -5% in 2½% steps with facilities for padlocking in any position
  • EA TS 35-1 terminal height = 1600 kVA
  • HV cable box - 3 pole single gland air filled shroud
    insulated compliant with EN 50336 and BS 2562
  • LV cable box – 4 pole multi gland air insulated, suitable for single core cables compliant with EN 50336 and BS 2562
  • LV Neutral terminal fully rated
  • Skid type under base complete with haulage
    holes
  • 2 lifting lugs = 1000 kVA 4 lifting lugs > 1000kVA
  • Earth terminals located beneath cable boxes
  • Filler port
  • Prismatic liquid level indicator
  • Drain valve
  • Aluminium rating plate
  • Thermometer pocket ¾” BSP
  • Desiccant breather
  • Jacking points

OPTIONAL ACCESSORIES

  • Dial type oil temperature indicator fitted to the thermometer pocket with up to 2 volt free normally open contacts
  • Liquid retention bund with or without sump or pump
  • Dial type winding temperature indicator fitted to the thermometer pocket with up to 2 volt free normally open contacts
  • Synthetic ester coolant
  • Hermetically sealed
  • Conservator
  • Alternative paint and colour systems
  • Close coupled LV and HV switchgear
     